BENNING DB 2 | Demonstration case for the practice-oriented application and training of VDE 0100 installation test devices.
Portable case for simulating safety tests on electrical systems in accordance with DIN VDE 0100/0105
Realistic representation of a low-voltage installation in a single-family house (TN / TT system)
Real components, such as FI circuit breaker, Schuko socket, on / off switch with light and current measuring loop, for load current measurement (A) of a boiler
Simulated components with connection terminals for equipotential bonding rails, earth electrodes, water pipes and lightning rods
Error simulation (good / bad) adjustable via 5 toggle switches
Measurement option for protective conductor (RPE), insulation resistance (RISO), loop (ZL-PE) and line impedance (ZL-N)
30 mA FI circuit breaker for measuring the tripping time, tripping current and contact voltage
Different measuring methods can be used for earth measurement (2- / 3- / 4-wire measuring method and skewerless using a current clamp)
Earthing contact socket for measuring voltage, frequency and single-pole testing of the outer conductor (phase)
Robust and dust-tight housing design
Power supply: 230 V, 50/60 Hz mains connection
Dimensions / weight: 450 x 330 x 110 mm, approx. 3.5 kg
Benning today offers a comprehensive range of high-quality testing, measuring, and safety devices that meet the standards and practical needs of professional users. The high quality standards of these devices are designed to meet the requirements of professional users.