Benning IT105 | Installation tester / test device, VDE 0100/0105, FI test RCD (044105)
Manufacturer number: 044105
BENNING 044105 | VDE 0100/0105 installation tester IT105.
- Display: graphic display (illuminated)
- Low resistance measurement: 0.15 Ω… 199 Ω
- Insulation resistance: 0.20 MΩ ... 199 MΩ
- Loop impedance (L-PE): 0.20 Ω… 1999 Ω
- Line impedance (LN / L): 0.20 Ω… 1999 Ω
- Short-circuit current: up to 26 kA
- FI / RCD test: tripping time (½ x, 1 x and 5 x IΔN, AUTO), tripping current (ramp)
- Test current: sinusoidal (AC), pulsating (A), 10/30/100/300/500 mA
- Phase sequence test: right / left
- Voltage: 1 V… 440 V
- Frequency: 45 Hz ... 65 Hz
Technical Data
All-current sensitive RCDs type B, B+: | No |
---|---|
Article number: | 044105 |
Automatic test sequence: | No |
Check residual voltage: | No |
Counter start-up: | No |
DIN VDE 0100 / IEC 60364-6: | Yes |
Dimensions (L x W x H) (mm): | 115 x 230 x 103 |
Insulation measurement 50V: | No |
Insulation measurement 100V: | No |
Insulation measurement 250V: | Yes |
Insulation measurement 325V: | No |
Insulation measurement 500V: | Yes |
Insulation measurement 1000V: | Yes |
Interfaces: | No |
Measured value memory: | No |
Mobile: | Yes |
Model: | Benning IT 105 |
Rotating field direction: | Yes |
Selective, SRCDs, PRCDs, type G/R: | No |
Software included: | No |
Stationary: | No |
Touch Display: | No |
Voltage drop: | No |
Weight (kg): | 1.5 |
e-Mobility (prepared): | No |
Documents & Downloads
Description
IT105 | Installation tester / test device, VDE 0100/0105, FI test RCD (044105)
The Benning installation tester IT105 enables you to carry out a simple and efficient safety test on electrical systems after installation, modification or as a regular repeat test in accordance with VDE0100 / 0105.
The installation tester is very easy to use: all measuring functions can be selected directly using the rotary switch. The large graphic display (95 x 55 mm) with backlighting makes operation easier and is very easy to read even in dark environments.
The Benning IT 105 has an AUTO start function for low-resistance, loop and line impedance measurements as well as a LOCK function for continuous measurements of the insulation resistance. The measuring process can be started directly using the test button on the test probe.
Measurement functions:
- Low resistance of protective conductor and equipotential bonding connections (test current: 200 mA)
- Insulation resistance with test voltage of 250 V, 500 V and 1000 V
- Loop impedance (L-PE) without FI / RCD tripping (NO-TRIP) with simultaneous display of the fault current (PFC)
- Line impedance (LN / L) with high test current (HIGH CURRENT) with simultaneous display of short-circuit current (PSC)
- Testing of RCDs, standard and delayed (S) with sinusoidal (AC) and pulsating test current (A)
- Automatic measurement of the tripping time (½ x, 1 x and 5 x IΔN) and the tripping current using the ramp method
- Voltage and frequency measurement up to 440 V.
- Three-phase direction test in three-phase networks (L1-L2-L3)
Lieferumfang
- Hard case
- Test tip with TEST button
- Probe / crocodile clip set
- Test lead with safety plug
- Shoulder strap
- 6 x 1.5 V mignon batteries
- Calibration certificate
Accessoires (4 products )
Alternate products (3 products )
Recommendations (2 products )
News and Knowledge
dataTec unboxed is the new video series from dataTec for product presentations and news from the world of measurement an...
The DIN VDE regulations govern the electrotechnical regulations as defined by DGUV V3 (accident prevention regulations f...
Thomas Schleich is an engineer, an expounder of ideas, a free spirit – and a first-class speaker at the dataTec Academy....