The Chauvin Arnoux CA 6547 insulation meter is a robust, construction site-friendly instrument that is optimized for the quantitative and qualitative testing of insulation. With a test voltage of up to 5000 V, the CA 6547 offers a comprehensive measuring range.
In addition to the insulation resistance, the tester also displays voltages, capacities and residual currents. It has four predefined test voltages: 500, 1000, 2500 and 5000 V. In addition, the test voltage can be programmed from 40 V to 5100 V in 10 V or 100 V steps.
The CA 6547 has a large-format, illuminated LCD display. It carries out a qualitative insulation test and automatically calculates the parameters DAR, PI, DD and plots the R (t) curve.
Other functions include a programmable test duration, limiting the test voltage to safe values, smooth, programmable alarms and much more. The CA 6547 is powered by NiMH batteries, which provide approximately one month of operation with 10 DAR and 5 PI measurements per day.
The device complies with the installation categories IEC 61010-1 CAT III 1000 V or CAT I 2500 V and IEC 61557.